Get Your Serial DF1 PLC Data into a BACnet MS/TP Network

Easily map your legacy PLC data into a BACnet MS/TP Master

SKU: 460BMSDFM

460BMSDFM

$NZD 1,468.72 - $NZD 1,655.37

Clear

Please note, site orders are made via credit card. Please contact sales@techstep.co.nz if you require support to purchase directly.

Product Description

Map Your Legacy PLC Data Tables Into a BACnet MS/TP Master
You can now make your legacy serial PLCs look like a BACnet MS/TP device! Any of your old, serial PLCs like the PLC5, SLC, or MicroLogix can now provide data to a BACnet/ MS/TP building automation system.

It’s the perfect tool to keep those old legacy PLCs from the scrap pile.

How Do I Use the 460BMSDFM in My Application?
For most applications, the mapping is very straight forward. PLC data table values like N7:200 and F9:1 are mapped directly to BACnet Analog and Binary values.

No message instructions and no ladder logic changes are required to monitor the PLC data on BACnet MS/TP.

It really is that simple.

Why Use Real Time Automation as a Gateway Supplier?
While there are certainly a number of other companies offering gateways, there is no one who provides the level of support and service that you receive from RTA.

When you call, a live person answers the phone. When you talk with sales, you will get honest answers and recommendations. When you get support, it is from an engineer who had a hand in the product’s development, and support doesn’t require a ticket or 24-hour wait.

Try the RTA difference today.

  • Manual
  • 3’ power cable with flying leads
  • 5-year hardware warranty
  • IPSetup software — automatically locates RTA gateway on the network
  • Unlimited firmware feature upgrades for life
  • CAT5 cross over cable for direct connection to PC during programming
  • Complete, unlimited access to our industry leading support staff

BACnet MS/TP Slave Features

BACnet/ MS/TP Operation Modes: BACnet MS/TP Master Responder
Supported Object Types: Device, Binary I/O, Analog I/O, Character String Value
Supported Service Codes: Read & Read Multiple-B, Write & Write Multiple-B, COV & COV unsolicited-B, Device Dynamic Binding, Dynamic Object Binding-B, Device Communication Control-B
Maximum Connections: 1
Analog Objects: Supported 1200 Input and 1200 Output
Binary Objects: Supported 1600 Input and 1600 Output

DF1 Master Features

Operation Modes: DFM Full Duplex and DFM Half Duplex
PLCs Supported: MicroLogix 1000, SLC 5/03 5/04 5/05, most PLC5s
Maximum number of Devices supported: 1 in Full Duplex Mode, 32 in Half Duplex
Data Type Supported: 100 Integers or 100 Binaries, or 50 floats, 82 character string per scan line
Scan lines: 100 input, 100 output
Physical Connections: RS485 and RS232

Gateway Security
You can configure up to nine different users with access to diagnostic and configuration screens.

Alarming
Set <, <=, >=, >, ==, !=, and Change-of-State rules on any data moving through the gateway. If alarm rule is triggered an email notification can be sent.

Translation Table
Allows for data manipulation during protocol translation. Scaling and other data format changes can occur in the gateway.

Status and Counters
Protocol specific status, counters and error messages are accessible within the gateways diagnostics page. They can also be delivered to a connected device.

Diagnostic Logging Page
Allows users to see and log start up sequences, protocol specific messages & error messages.

460BMSDFM-N34
DATASHEET  USERGUIDE
460BMSDFM-N700
DATASHEET  USERGUIDE