Connect DeviceNet Slave to BACnet MS/TP

Easily Connect DeviceNet Slaves to BACnet MS/TP Slaves

SKU: 460DMBM

460DMBM

$NZD 1,503.40 - $NZD 1,558.72

Clear

Please note, site orders are made via credit card. Please contact sales@techstep.co.nz if you require support to purchase directly.

Product Description

Get Your DeviceNet Slave Devices Connected Directly to Your BACnet MS/TP Slave Devices
The 460DMBM moves data between a network of up to 32 DeviceNet Slaves and up to 32 BACnet MS/TP Slave devices. With the 460DMBM you are making a direct connection between DeviceNet data and BACnet MS/TP Binary and Analog objects.

How Do You Map the Data?
Up to 400 bytes of DeviceNet data per Slave device will be mapped into your BACnet MS/TP Slaves. DeviceNet data will be mapped into your BACnet MS/TP Slaves as Binary and Analog BACnet MS/TP objects. When writing from your BACnet MS/TP Slaves to your DeviceNet Slaves, up to 128 Binary BACnet MS/TP Objects per Scan line will be viewed as DeviceNet data.

It’s really that simple. Need to modify your data as it passes from one protocol to the other? No problem. Each data mapping you apply can be modified with up to 3 mathematic functions. Add 4 to a value, multiply by 4 and divide by 10 with ease.

Why use Real Time Automation as a Gateway Supplier?
The 460DMBM provides an option to access DeviceNet Slave devices without having to upgrade your established BACnet MS/TP system. While there are certainly a number of other companies offering stand alone gateways, there is no one who provides the level of support and service that you receive from RTA.

  • Manual
  • 3’ power cable with flying leads
  • 5-year hardware warranty
  • IPSetup software — automatically locates RTA gateway on the network
  • Unlimited firmware feature upgrades for life
  • CAT5 cross over cable for direct connection to PC during programming
  • Complete, unlimited access to our industry leading support staff

DeviceNet Master Features

DeviceNet Operation Modes: UCMM Client, Group 2 Client, Group 2 only Client
Implicit Message Support: Polled only, Assembly Object
Maximum DeviceNet Slave Devices: 32
Data per Slave: 0-400 Bytes in each direction
Supported Data Types: BIT8, BIT16, BIT32, INT8, INT16, INT32, INT64, UINT8, UINT16, UINT32, UINT64, Float, Double

BACnet MS/TP Master Features

BACnet/ MS/TP Operation Modes: BACnet MS/TP Master Initiator
Supported Object Types: Device, Binary, Analog, Multi-State, Character String Value
Supported Service Codes: Read Property-A, Read Property Multiple-A, Write Property-A, Write Property
Multiple-A, Device Dynamic Binding-A
Maximum Connections: 32
Number Read/Write Scan Lines per Device: 200 Total - 100 reads & 100 writes
Scan Line Support: Up to 128 Total Objects

Gateway Security
You can configure up to nine different users with access to diagnostic and configuration screens.

Alarming
Set <, <=, >=, >, ==, !=, and Change-of-State rules on any data moving through the gateway. If alarm rule is triggered an email notification can be sent.

Translation Table
Allows for data manipulation during protocol translation. Scaling and other data format changes can occur in the gateway.

Status and Counters
Protocol specific status, counters and error messages are accessible within the gateways diagnostics page. They can also be delivered to a connected device.

Diagnostic Logging Page
Allows users to see and log start up sequences, protocol specific messages & error messages.

460DMBM-N34
DATASHEET  USERGUIDE