Connect BACnet MS/TP Devices to an EtherNet/IP Scanner

Easily connect up to 32 BACnet MS/TP Responder devices to an EtherNet/IP Scanner Device

SKU: 460ESBM

460ESBM

$NZD 1,400.11 - $NZD 1,992.35

Clear

Please note, site orders are made via credit card. Please contact sales@techstep.co.nz if you require support to purchase directly.

Product Description

Connect BACnet MS/TP Slaves to an EtherNet/IP Scanner Device
The 460ESBM moves data between a network of up to 32 BACnet MS/TP devices and an EtherNet/IP Scanner. It’s the perfect tool to tie your BACnet MS/TP devices to your EtherNet/IP system.

How Do I Use the 460ESBM in My Application?
Up to 480 bytes of data can be mapped in each direction between the protocols. That means you can report up to 480 bytes of data between 1-32 BACnet MS/TP devices and you can also write up to 480 bytes of data to 1-32 BACnet MS/TP devices.

It’s really that simple. Need to modify your data as it passes from one protocol to the other? No problem. In each data mapping you can apply up to 3 mathematic functions. Add 4 to a value, multiply by 2 and divide by 10 with ease.

Why Use Real Time Automation as a Gateway Supplier?
The 460ESBM provides an option to connect BACnet MS/TP devices to your EtherNet/IP system. While there are certainly a number of other companies offering stand alone gateways, there is no one who provides the level of support and service that you receive from RTA.

When you call, a live person answers the phone. When you talk with sales, you will get honest answers and recommendations even if that means recommending someone else’s solution. When you get support, it is from an engineer who had a hand in the product’s development, and support doesn’t require a ticket or 24 hour wait. We are unashamed of the fact that we are a smaller company because that means you mean a lot more to us.

  • Manual
  • 3’ power cable with flying leads
  • 5-year hardware warranty
  • IPSetup software — automatically locates RTA gateway on the network
  • Unlimited firmware feature upgrades for life
  • CAT5 cross over cable for direct connection to PC during programming
  • Complete, unlimited access to our industry leading support staff

BACnet MS/TP Master Features

BACnet/ MS/TP Operation Modes: BACnet MS/TP Master Initiator
Supported Object Types: Device, Binary, Analog, Multi-State, Character String Value
Supported Service Codes: Read Property-A, Read Property Multiple-A, Write Property-A, Write Property
Multiple-A, Device Dynamic Binding-A
Maximum Connections: 32
Number Read/Write Scan Lines per Device: 200 Total - 100 reads & 100 writes
Scan Line Support: Up to 128 Total Objects

Ethernet/IP Adapter Features

Operation Modes: EtherNet/IP Adapter
Message Support: Implicit, Explicit UCMM
Data Types: BIT8,16 & 32; INT8, 16, 32 & 64; UINT8,16, 32 & 64; Float & Double
Maximum EtherNet/IP Scanner Devices: Up to 10 can listen, only one can write I/O
Max Data Per Adapter Connection: Up to 480 bytes in each direction

Gateway Security
You can configure up to nine different users with access to diagnostic and configuration screens.

Alarming
Set <, <=, >=, >, ==, !=, and Change-of-State rules on any data moving through the gateway. If alarm rule is triggered an email notification can be sent.

Translation Table
Allows for data manipulation during protocol translation. Scaling and other data format changes can occur in the gateway.

Status and Counters
Protocol specific status, counters and error messages are accessible within the gateways diagnostics page. They can also be delivered to a connected device.

Diagnostic Logging Page
Allows users to see and log start up sequences, protocol specific messages & error messages.